Google Cloud's October 2026 London Outage Explained: Why Backup Power Failed

19 min readUpdated By Saket Bhatnagar

Researched and drafted with AI, reviewed and edited by Saket Bhatnagar.

In short

  • The Google Cloud outage Europe woke up to on 20 October 2026 hit one London zone, not the continent. A zone is one deployment area inside a cloud region, meant to fail on its own; this one was europe-west2-b.
  • Google's final report says an underground cable fault cut one of the site's two mains power feeds. The other feed was already switched off for repairs.
  • The controller that should start the diesel generators checked for voltage in the wrong place. It saw live power on the utility side of feed B's open switch, so the generators never started and five minutes of battery ran out.
  • The other two London zones slowed as well. Work that moved to them automatically, called failover, overloaded them, and some failovers failed, partly for lack of spare capacity.
  • Beginners can stop after the section on why the other zones slowed. Engineers then get which resources survive a zone loss, a runnable spare-capacity sum, a zone-loss test plan and where Google's own documents disagree.

What goes wrong when one cloud zone loses all its power?

Everything you placed only in that zone stops, and things spread across zones can still slow down. If you searched for a Google Cloud outage Europe-wide on 20 October 2026, the real story is smaller and more useful.

Google's final report says one data centre facility, the one hosting zone europe-west2-b in London, lost power. Customers saw impact for 6 hours and 8 minutes. Google says it found no impact outside the europe-west2 region.

Picture a common setup. A payments app for UK customers runs its web servers on a few virtual machines in europe-west2-b, with one database in the same zone. The setup is made up, but the zone, times and failure are from Google's report. At 07:00 London time (11:30 in India) both stopped answering, and nothing in the app's own code was wrong.

This guide follows that app. You will see why the backup power failed and why the other zones suffered. Then you will see how to build and test the app so that losing a zone hurts less.

Which words do you need before reading Google's incident report?

You need a handful of cloud words and a handful of power words. Each gets one plain line here.

  • Region: a geographic area, such as London, made of several zones. Google lists europe-west2 as London.
  • Zone: a deployment area inside a region. Google's docs say zones should be treated as a single failure domain, meaning one thing that can fail as a unit.
  • Zonal resource: something that lives in one zone, like a single virtual machine (VM). Regional resource: something Google spreads across zones for you, like a regional instance group.
  • Failover: moving work automatically from a failed place to a healthy one.
  • Control plane: the part of a cloud that creates, changes and deletes resources, as opposed to the part that serves your traffic. You reach it through an API, the interface programs use to call a service.
  • Utility feed: a power line from the electricity company. This site had two, called feed A and feed B.
  • Breaker: a heavy-duty switch on a feed. Opened and locked, it lets no power through, even when the utility side is still live.
  • UPS (uninterruptible power supply): batteries that carry the load for a short time. Here they lasted 5 minutes.
  • PLC (programmable logic controller): a small industrial computer. Here it decided when to start the diesel generators.

Was the Google Cloud outage Europe-wide in October 2026?

No. Google's final report says it did not find any impact outside the europe-west2 region. Inside that region, one zone went down completely and the other two were slowed by the fallout.

Press coverage still made it feel bigger. A PA Media report quoted Revolut as saying it had "a service disruption affecting multiple services". The reporter wrote that the issue was understood to be linked to Google Cloud. Google's report names no customers.

The timeline in Google's own times

Google's report uses US Pacific time, and it adds London times to each entry. The table gives London and India times too, converted with Python's time zone database.

Key moments from Google's final incident report (19 to 20 October 2026)
US PacificLondon (BST)India (IST)What happened
22:53, 19 Oct06:53, 20 Oct11:23Feed A fails from an underground cable fault; generators do not start
23:0007:0011:30Batteries run out and impact begins
23:0407:0411:34Google engineers alerted by automated monitoring
23:0907:0911:39Automatic failover to other zones begins
23:5407:5412:24Power from a standby utility source restored; power restoration to the data hall begins
03:45, 20 Oct11:4516:15Traffic slowly let back into europe-west2-b
04:2912:2916:59First phase ends; regional services fully undrained, meaning traffic flows to the zone again
05:0813:0817:3899.5% of VMs healthy and creating new VMs fully supported

Look at the gap between power and recovery. Standby power was back within an hour, and the data halls had power by 00:20. Storage devices that shut down uncleanly then needed recovery, and traffic was let back in gradually.

Why did the backup generators not start?

Because the PLC thought the site still had a live power feed. Its voltage sensor for feed B sat on the utility side of a breaker that was locked open, so it read voltage that never reached the building.

How the site was set up that night

The facility normally runs on two utility feeds. On 14 October 2026 a quarterly generator load test found issues, and feed B's breaker was opened and locked for repairs. From then on, feed A carried the whole load alone.

At 22:53 Pacific on 19 October, an external underground cable fault on the utility network killed feed A. The UPS batteries took over at once. Google's report says they provide 5 minutes of runtime.

What the controller saw

Google's report says the PLC was programmed to check whether voltage was present on the feeder before commanding a generator start. Its undervoltage sensing for feed B was wired upstream, on the line side, of feed B's breaker.

So the sensor saw healthy voltage on a line that was cut off from the building by the open breaker. The report calls this a misconfiguration of PLC logic that did not check both an undervoltage condition and the physical breaker position. Breaker position is the missing check from the prediction above. The generators stayed off, the batteries drained, and the data halls, the rooms full of servers, lost all power.

Why the generators never started

Follow feed B: the sensor reads voltage before the locked breaker, so the PLC sees power that never reaches the halls.

Diagram connections:

  • Utility feed B to Feed B voltage sensor (Voltage present)
  • Utility feed B to Feed B breaker (Stops at the open breaker)
  • Feed B voltage sensor to PLC (Reports: feed B is live)
  • PLC to Diesel generators (No: do not start)
  • Utility feed A to UPS batteries (Feed lost, batteries take over)
  • UPS batteries to Data halls for zone b (Drained after 5 minutes)
  • Utility feed A: Cut at 22:53 by an underground cable fault
  • Utility feed B: Live from the utility, but isolated
  • Feed B voltage sensor: Wired on the line side of the breaker
  • Feed B breaker: Opened and locked for repairs since 14 Oct
  • PLC: Decides on a generator start from feed voltage
  • Diesel generators: Never told to start
  • UPS batteries: 5 minutes of runtime, then empty
  • Data halls for zone b: Lose all power at about 23:00

Power came back a different way. At 23:54 the team began restoring power from a standby utility source, and data hall power was re-established at 00:20.

An everyday picture: a housing society's water supply

Think of a society that gets water from two municipal lines and has a borewell pump for emergencies. A small controller starts the pump only when it sees no pressure on any municipal line.

Mapping the water picture to the power failure
Society waterData centre power
Municipal line A burstsFeed A cut by a cable fault
Line B's valve shut for repair workFeed B's breaker opened and locked
Pressure gauge fitted before the shut valveFeed B sensor wired on the line side of the breaker
Pump controller sees pressure and waitsPLC sees voltage and does not start the generators
Overhead tank drains, taps run dryUPS batteries drain, servers lose power

Where the picture breaks: a water tank lasts hours, while these batteries lasted 5 minutes by design. A real PLC also reads many signals, and the report's fix is to check breaker position as well as voltage.

Why did one zone's failure slow down the other London zones?

Because the work did not disappear; it moved. From 23:09 Pacific, Google's routing and customers' own apps failed over to zones a and c, and that sudden demand saturated them.

The report names two main causes for impact outside zone b. The first is instant demand surges on the neighbouring zones. The second is control-plane dependencies that crossed zone boundaries.

  • Demand surge: redirected queries, high-availability database failovers and moved compute work filled the spare compute in the other zones.
  • Cross-zone dependencies: some regional control planes called metadata and catalog components in the offline zone. Those calls timed out, so job submissions stalled and API responses slowed.
  • Errors: customers saw intermittent HTTP 500 and 503 errors across the region. Both codes mean the server failed or was too busy to answer.
  • Lost control: for a while, some regional resources could not be created, updated or deleted.

How one zone's power loss spread inside europe-west2

Notice the two separate paths into zones a and c: moved traffic that overloads them, and control-plane calls that still wait on zone b.

Diagram connections:

  • Zone b loses power to Automatic failover (Traffic must go somewhere)
  • Automatic failover to Zones a and c (Sudden demand surge)
  • Zones a and c to Spare capacity runs out (Saturated)
  • Zone b loses power to Regional control planes (Dependency now missing)
  • Regional control planes to Timeouts and stalls (Cross-zone calls time out)
  • Zone b loses power: About 23:00 Pacific, 07:00 London
  • Automatic failover: Google routing and client apps, from 23:09
  • Zones a and c: Take the moved work on top of their own
  • Spare capacity runs out: Some failovers fail, 500 and 503 errors
  • Regional control planes: Some calls still go to parts in zone b
  • Timeouts and stalls: Some regional resources cannot be changed

Back to the payments app. Even if it had kept a copy in zone a, its failover would have joined that rush for capacity. The report says some failovers were unsuccessful due to capacity constraints and difficulty in replicating the underlying storage mechanism.

Which Google Cloud resources survive losing one zone?

Regional resources are designed to survive it; zonal resources do not unless you build a copy in another zone. Google's reliability guide says a failure in a zone might affect the zonal resources provisioned in that zone.

The report says the same for VMs. Compute Engine zonal resources need customers to provision failover or cross-zone recovery resources if needed. In other words, a single VM in zone b is your problem to protect.

Resource scope (from Google's reliability guide) against what the 27 October report says happened
ResourceScopeWhat the report says
Single VM or zonal instance groupZonalZonal resources in europe-west2-b were unavailable in the first phase
Regional managed instance groupRegional, spread over zonesNot named; docs say other zones keep serving
Cloud SQL without high availabilityZonalNon-HA instances and read replicas in zone b were hit
Cloud SQL with high availabilityZonal primary plus standby in another zoneHA database failovers were part of the load surge
BigtableA single-cluster instance sits in one zoneSingle-cluster instances in zone b were hit
GKE (managed Kubernetes)Zonal or regional clusterZonal control planes and nodes in zone b were hit
Regional Persistent DiskRegional productListed among products that degraded outside zone b

Read the last column carefully. Regional did not mean untouched. The report says products outside zone b saw degradation and failover issues, driven by sudden compute capacity exhaustion.

One more detail matters for planning. Google's geography page says each region has three or more zones in three or more physical data centres. It names Stockholm, Osaka and Montreal as exceptions, with three zones in one or two data centres, as of 26 October 2026. In those regions, two zones can share a building.

How much spare capacity do you need to survive losing a zone?

Enough that the zones left can carry the full load by themselves. With three zones that means about 50% extra; with two zones it means double.

Google's regional instance group docs explain why spare capacity must already be running. When a zone fails, the instances in the remaining zones keep serving. No new instances are added and none are redistributed unless you set up autoscaling.

Autoscaling, which adds VMs when load rises, sounds like the answer. But it needs fresh capacity in zones a and c at the exact moment everyone else wants it, and the report shows that capacity ran short. Spare VMs that are already running do not have to win that race.

The script below does the sums. It uses Google's published availability targets and the outage length from the report. It runs on Python 3.13 with no extra packages.

python
import math

# Targets from Google's "Building blocks of reliability" page
targets = {"single zone": 0.999, "multi-zone": 0.9999, "multi-region": 0.99999}
month_s = 30 * 24 * 60 * 60  # seconds in a 30-day month

for name, t in targets.items():
    down_s = (1 - t) * month_s
    print(f"{name}: {down_s / 60:.1f} min ({down_s:.0f} s) of downtime a month")

outage_min = 6 * 60 + 8  # 23:00 to 05:08 US/Pacific, from Google's report
single_zone_min = (1 - 0.999) * month_s / 60
print(f"outage: {outage_min} min = {outage_min / single_zone_min:.1f} months "
      f"of a single-zone budget")

def vms_to_run(needed, zones):
    per_zone = math.ceil(needed / (zones - 1))  # one zone may vanish
    return per_zone * zones, per_zone

for zones in (2, 3):
    total, per_zone = vms_to_run(20, zones)
    print(f"{zones} zones: run {total} VMs, {per_zone} per zone, "
          f"{total / 20 - 1:.0%} extra")

Running it prints exactly this:

text
single zone: 43.2 min (2592 s) of downtime a month
multi-zone: 4.3 min (259 s) of downtime a month
multi-region: 0.4 min (26 s) of downtime a month
outage: 368 min = 8.5 months of a single-zone budget
2 zones: run 40 VMs, 20 per zone, 100% extra
3 zones: run 30 VMs, 10 per zone, 50% extra

Two warnings keep this honest. Google's page says these percentages are targets, and service SLAs can differ. The sum also assumes each zone holds an equal share of the VMs.

For the payments app, the fix is now concrete. It needs 20 web VMs at peak, so it runs a regional group of 30 across three zones. Its database moves to Cloud SQL with high availability, which keeps a synchronous standby in another zone and fails over automatically.

How do you test that your app survives a zone outage?

Take a zone away on purpose, in a controlled window, and watch whether the rest carries full load. Google's docs include a page on simulating a zone outage for a regional instance group, built for exactly this check.

That page's script stops and starts Apache, a web server, on the VMs by default. You replace those commands with your own failure and recovery. The steps below wrap it in a full drill.

  1. List what lives in each zone

    Mark every VM, disk, database and cluster as zonal or regional. Anything zonal with no copy elsewhere is a single point of failure.

  2. Find hidden cross-zone dependencies

    Ask what your recovery needs: new VMs, deploys or config changes. The report shows creating and changing resources can fail during a zone outage.

  3. Run the zone-outage simulation

    Use the script from Google's simulation page, with your own failure command, to take one zone's instances out. Keep real traffic or a load test running.

  4. Measure against the spare-capacity sum

    Check that latency and the rate of 500 and 503 errors stay within your targets, with one zone gone and no autoscaling help.

  5. Repeat while something is already broken

    Run the drill during planned maintenance too. This outage struck while one power feed was out for repairs.

  6. Practise who says what

    Rehearse the runbook and the customer message. Google's own fixes include an automated alert-to-communication mechanism.

What did Google change after the October 2026 outage?

Google fixed the controller first and listed the rest, mostly with estimated dates. The table shows each action's status as written in the final report of 27 October 2026.

Preventive actions in Google's final report (status as of 27 October 2026)
ActionStatus in the report
PLC reconfigured and validatedDone on 20 October and again on 26 October
Emergency operating procedures updatedDone on 26 October
Procedures practised twice per shiftDone from 24 October, checked daily
Utility repairs the cable and restores feed AEstimated 30 October
Return to both feeds and retest generator transferEstimated 31 October
Full PLC code review and resiliency testingEstimated 31 October
Freeze planned maintenance at similar sites and add stricter approvalsEstimated 30 October
Check PLC setups at sites with similar topologies and PLC makersEstimated 15 November
Automated alert-to-communication for location-wide incidentsNo date given
Wider platform testing for infrastructure-level eventsNo date given

Where Google's own documents disagree

Google's status updates of 20 October, the preliminary report of 22 October and the final report of 27 October differ in places. None of these change the lesson, but they matter if you quote numbers.

  • Cause: the preliminary report described a power grid disruption and a PLC that failed to start the generators. Only the final report mentions the cable fault and the line-side wiring.
  • Times: the preliminary report gives 23:08 for detection and 05:10 for the end. The final report's timeline gives 23:04 and 05:08.
  • Looker Studio: status updates on 20 October said Looker Studio was not impacted. Both reports' lists of impacted services include it.

These differences are as of 28 October 2026. Quote the final report, and say which document a number came from.

How is this different from the Cloud Storage outage earlier in October 2026?

It is a different incident with a different lesson. On 8 and 9 October, a configuration change to storage load balancing in us-central1 (Iowa) bypassed capacity-aware routing and caused failed writes.

That outage taught you to retry safely. This one teaches you where to place things, because no retry helps when every copy sits in one dark zone. Read them together: retries handle short, partial failures, and multi-zone design handles a whole zone going away.

How do you explain the Google Cloud zone outage in a system design interview?

Tell it as a chain of causes, then turn each link into a design choice.

  1. State the scope

    One zone in Google's London region lost power, and customers saw 6 hours 8 minutes of impact. The rest of the region degraded; Google found no impact outside it.

  2. Name the chain

    One feed was out for repair, the other was cut, and the generator controller sensed voltage on the wrong side of a locked breaker.

  3. Explain the spread

    Failover moved work into the other zones at once, and some regional control planes still depended on the dead zone.

  4. Design for it

    Spread across three zones with 50% spare capacity, use regional or HA versions of stateful services, and do not rely on creating resources mid-outage.

  5. Prove it

    Run a zone-outage drill, including during maintenance, and measure errors and latency with one zone gone.

Questions people ask

Was the October 2026 Google Cloud outage Europe-wide?
No. Google's final report says it found no impact outside the europe-west2 region, which is London. One zone, europe-west2-b, lost power, and the region's other two zones were slowed by failover demand and cross-zone dependencies.
Why did Google's backup generators not start?
The controller that starts them saw voltage that was not really available. Feed B's breaker was locked open for repairs, but its voltage sensor sat on the utility side of that breaker. The controller concluded a feed was still live, so it never started the generators, and the 5-minute batteries ran out.
How long did the Google Cloud London outage last?
Google's final report gives 6 hours and 8 minutes of impact, from 23:00 on 19 October to 05:08 on 20 October, US Pacific time. That is 07:00 to 13:08 in London and 11:30 to 17:38 in India. The preliminary report said 6 hours and 10 minutes, ending at 05:10.
Would a multi-zone setup have avoided the impact completely?
It would have kept you running, but probably not untouched. The other London zones saw demand surges, intermittent 500 and 503 errors, and slow control-plane actions. I'd expect a multi-zone app with spare capacity already running to ride that out far better than one that must create new VMs mid-outage.
Do I need multiple regions instead of multiple zones?
It depends on how much downtime you can accept. Google's reliability guide gives targets of 99.99% for multi-zone and 99.999% for multi-region deployments. Multi-zone covers a zone loss like this one; multi-region also covers a whole-region failure, at higher cost and complexity.
Is this the same incident as the Google Cloud Storage outage in October 2026?
No. The Cloud Storage outage hit writes in us-central1 on 8 and 9 October after a routing change skipped capacity checks. This incident was a power failure in one London zone on 20 October, London time. They share a lesson about capacity, but their causes differ.

Sources and further reading